UL / FM / AWWA Wet-Barrel Fire Hydrant
Specifications:
● Manufactured in accordance with AWWA C503 Standard
● UL Listed / FM Approved
● (1) 4.5” Pumper Nozzle, (2) 2.5” Hose Nozzles
● Nozzle Threads to NFPA 1963 Standard.
● Flange to ANSI B16.1, Class 125 (6”). Other types available upon request
Working pressure:
250PSI for FM approval.
200PSI for UL listed.
Working temperature:
42° F – 180° F
Corrosion protection:
Interior and exterior is e-coated to a dry film thickness of 0.6
mils minimum, then fusion bonded epoxy powder coated (FBE).
UL / FM / AWWA Wet-Barrel Fire Hydrant Material Specifications:
Part Name | Material | ASTM Spec. |
---|---|---|
Body | Ductile Iron | A536 65-45-12 |
Pumper Nozzle Cap | Cast Iron | A126 Class B |
Pumper Nozzle | Bronze | B62 C83600 |
Main Valve | Rubber | NBR |
Main Valve Holder | Stainless Steel | AISI 304 |
Hose Nozzle Cap | Cast Iron | A126 Class B |
Packing | Graphite | Commercial |
Hose Nozzle | Bronze | B62 C83600 |
Stem | Stainless Steel | AISI 304 |
Stem Nut | Bronze | B62 C83600 |
Operating Nut | Bronze | B62 C83600 |
O-ring | Rubber | NBR |
Pumper Nozzle Gasket | Rubber | NBR |
Hose Nozzle Gasket | Rubber | NBR |