UL / FM Alarm Check Valve, Vertical Trim (Flange x Flange)
Specification
- Valve must be installed in vertical position with the trim as shown.
Any deviation may affect the proper operation of the valve. - Flange designed to EN1092-2 PN10/16, ANSI B16 1 Class 125 or
BS10 Table D/E (Other types available on request). - UL listed.
Working pressure:
- Cold water, 300PSI,
- 200PSI or 250PSI available on request.
Corrosion protection:
- Internally and externally fusion bonded epoxy powder coated (FBE).
UL / FM Alarm Check Valve, Vertical Trim (Flange x Flange) Material Specifications:
No. | Part Name | Material | ASTM Spec. |
---|---|---|---|
1 | Body | Ductile Iron | A536 65-45-12 |
2 | Cover | Ductile Iron | A536 65-45-12 |
3 | Gasket | Rubber | EPDM |
4 | Bolt | Carbob Steel | A307B |
5 | Stem | Stainless Steel | AISI 304 |
6 | Spring | Stainless Steel | AISI 304 |
7 | Disc | Ductile Iron | A536 65-45-12 |
8 | Disc Ring | Rubber | EPDM |
9 | Seat | Bronze | B62 C83600 |
10 | Retainer | Brass | B16 C36000 |
11 | Bolt | Stainless Steel | A2-70 |